Function Parameter Index Reference
86 RS232 Communications Reference Manual 8/99
Static Configuration Parameters:
Table 5-55 ON/OFF Static Configuration Parameters
Parameter Index Type Description
pv_hi 0 REAL
pv High Range value –99999 to 99999 (default 100)
pv_lo 1 REAL
pv Low Range value –99999 to 99999 (default 0)
sp_hi_lim 6 REAL
set point high limit, -99999 to 99999 (default 100)
sp_lo_lim 7 REAL
set point low limit, -99999 to 99999 (default 0)
sp_rate_dn 9 REAL
Set point low rate of change limit, 0 (off) to 99999 (eu/min)
sp_rate_up 10 REAL
Set point high rate of change limit, 0 (off) to 99999 (eu/min)
devbar_hi 11 REAL High scale value for deviation bar graph (0 to 99999) (default
100)
devbar_low 12 REAL Low scale value for deviation bar graph [always = -devbar_hi]
Output
Hysteresis
13 REAL Off – 0 to 10% of Input Span
al_sp[4] 14-17 REAL alarm set points al1sp1, al1sp2, al2sp1, al2sp2, -99999 to 99999
(default 0)
al_hyst 22 REAL alarm hysterysis 0 to 5 (%)
Fail Safe Out 23 BOOL Fail Safe Out = On/Off