Function Parameter Index Reference
104 RS232 Communications Reference Manual 8/99
fRestartRamp 19 REAL C R/W ramp rate to use when power down restart is
in effect
fJogSeg 20 REAL C R/W segment jumped to on a pulse to JOG input
fLoopStart 21 REAL C R/W first segment in a loop – 0->no loop
fLoopEnd 22 REAL C R/W last segment in a loop – 0->no loop
fDispHiLim 28 REAL C R/W output high limit for display purposes only
fDispLoLim 29 REAL C R/W output low limit for display purposes only
bRampTime 31 BOOL C R/W TRUE = ramp time, FALSE = ramp rate
Dynamic Output Parameters:
Table 5-72 SPP Dynamic Output Parameters
Parameter Index Type Use R/W Description
STA 34 REAL O R program state {N/A, RESET, RUN, HOLD,
GHOLD, STOP}
SEG 35 REAL O R current segment number
PGM 36 REAL O R current program number
SP 37 REAL O R setpoint output ( EU)
AUX 38 REAL O R auxilary output (EU)
STMR 39 REAL O R time remaining in current segment (minutes)
STME 40 REAL O R time elapsed in current segment (minutes)
PTME 41 REAL O R time elapsed in program (minutes).
GHOLDI 42 BOOL O R set when program is in the GHOLD state
READY 43 BOOL O R set when program is in RESET state
RUNI 44 BOOL O R set when program is in RUN state
HOLDI 45 BOOL O R set when program is in HOLD state
STOPI 46 BOOL O R set when program is in STOP state