122 RS232 Communications Reference Manual 8/99
5.69 TPSC (3POS) Function Block
Description
The TPSC (3POS) label stands for Three Position Step Control operation. This block is part of the
Loops category. It looks like this graphically on the Control Builder.
Dynamic Parameters:
Table 5-90 TPSC Dynamic Parameters
Parameter Index Type Use R/W Description
status 0 REAL C R block status (see section 5.2 for code list)
lsp 1 REAL C R/W local set point (eu)
lsp2 2 REAL C R/W local set point 2 (eu)
rem_mode 3 BOOL C R/W remote set point mode request {OFF, ON}
man_mode 4 BOOL C R/W manual output mode request {OFF, ON}
man_out 5 REAL C R/W manual output value 0 to 100 (%)
tune_req 6 BOOL C R/W limit cycle auto-tuning request {OFF, ON}
rsp_eu 7 REAL C R remote set point in eu for monitoring
deviation 8 REAL C R Deviation in eu for monitoring
pv 9 REAL C R Process Variable in eu for monitoring
fbpct 10 REAL C R Percent feedback estimation for monitoring
DSP 11 REAL O R Display Set Point in eu for monitoring
MODE 12 REAL O R actual mode encoded per note 8