5.5 AI Function Block
Description
The AI label stands for Analog Input. This block is part of the Loops category. It looks like this
graphically on the Control Builder.
Dynamic Parameters:
Table 5-5 AI Dynamic Parameters
Parameter Index Type Use R/W Description
status 0 REAL C R Block Status (see section 5.2 for code list)
OUT 1 REAL O R analog input value (eu)
FAIL 2 BOOL O R Failed input indication
Static Configuration Parameters:
Table 5-6 AI Static Configuration Parameters
Parameter Index Type Description
filt_time 2 REAL filter time constant (seconds) {0-120} [default 0]
bias 3 REAL bias (eu).{-99999 to 99999} [default 0]
failsafe 4 REAL failsafe value (eu) [default 0]
range_hi 6 REAL high range value [default 0]
range_lo 7 REAL low range value [default 100]