Function Parameter Index Reference
8/99 RS232 Communications Reference Manual 53
5.15 CARB Function Block
Description
The CARB label stands for Carbon Potential. This block is part of the Loops category. It looks like this
graphically on the Control Builder.
Dynamic Parameters:
Table 5-18 CARB Dynamic Parameters
Parameter Index Type Use R/W Description
status 0 REAL C R block status (see section 5.2 for code list)
lsp 1 REAL C R/W local set point (eu)
lsp2 2 REAL C R/W local set point 2 (eu)
rem_mode 3 BOOL C R/W remote set point mode request {OFF, ON}
man_mode 4 BOOL C R/W manual output mode request {OFF, ON}
man_out 5 REAL C R/W manual output value –5 to 105 (%)
tune_req 6 BOOL C R/W limit cycle auto-tuning request {OFF, ON}
rsp_eu 7 REAL C R remote set point in eu for monitoring
deviation 8 REAL C R Deviation in eu for monitoring
PV 9 REAL O R Calculated Process Variable (Percent Carbon) for
monitoring
DSP 10 REAL O R Display Set Point in eu for monitoring
OUT 11 REAL O R control output –5 to 105 (%)
MODE 12 REAL O R actual mode encoded
All 13 BOOL O R Alarm 1
AL2 14 BOOL O R Alarm 2
DEWPT 15 REAL O R Calculated dewpoint [replaces BCO]
ATI 16 BOOL O R Auto Tune Indicator. ON = Auto Tune in progress
O2 17 REAL I R Oxygen sensor input (0 to 100%)
RSP 18 REAL I R Remote Set Point (% or eu per sp_units)