56 RS232 Communications Reference Manual 8/99
5.16 CMPR Function Block
Description
The CMPR label stands for Comparison Calculation. This block is part of the Calculations category. It
looks like this graphically on the Control Builder.
Dynamic Parameters:
Table 5-20 CMPR
Dynamic Parameters
Parameter Index Type Use R/W Description
status 0 REAL C R block status (see section 5.2 for code list)
XGY 1 BOOL O R X Greater than Y
XEY 2 BOOL O R X Equals Y
XLY 3 BOOL O R X Less than Y
X 4 REAL I R input 1
Y 5 REAL I R input 2
Static Configuration Parameters:
None