Function Parameter Index Reference
8/99 RS232 Communications Reference Manual 55
use_rpm 34 BOOL
Use minutes (0) or repeats per minute (1) for integral constant
sp_rate_dn 35 REAL
Set point low rate of change limit, 0 (off) to 99999 (eu/min)
sp_rate_up 36 REAL
Set point high rate of change limit, 0 (off) to 99999 (eu/min)
FF_GAIN 37 REAL
Feed forward gain, 0.0 to 10.0
RATIO 39 REAL
Gain value for Ratio PID (-20 to 20) (default 1) [ used when
RA_BIAS > 0]
LBIAS 40 REAL Bias value for Ratio PID when RA_BIAS = LOC_BIAS](-99999 to
99999) (0)
devbar_hi 41 REAL
High scale value for deviation bar graph (0 to 99999) (default 100)
devbar_low 42 REAL Low scale value for deviation bar graph [always = -devbar_hi]
L%CO 43 REAL Local percent carbon monoxide (2.0 to 35.0, default 20.0)
REM_CO 44 BOOL Use %CO input instead of local L%CO (default = OFF)
FURNACE_F
ACTOR
45 REAL Furnace Factor in %C (-0.5 to 0.5)
ANTI_SOOT 46 BOOL Anti-soot SP limit enable (default = OFF)
TEMP_LO_LI
M
48 REAL
Trigger value for LOTEMP Boolean output (0 to 2500
°
F)
PERCENT_H 50 REAL Percent hydrogen (1 to 100, default = 40)