Function Parameter Index Reference
8/99 RS232 Communications Reference Manual 105
Dynamic Input Parameters:
Table 5-73 SPP Dynamic Input Parameters
Parameter Index Type Use R/W Description
PV1 47 REAL I R process variable (EU), for deviation check
PV2 48 REAL I R 2
nd
process variable (EU), for deviation check
PV3 49 REAL I R 3
rd
process variable (EU), for deviation check
PV4 50 REAL I R 4
th
process variable (EU), for deviation check
NPGM 51 REAL I R program number (when SET is ON)
NSEG 52 REAL I R starting segment number (when SET is ON)
SET 53 BOOL I R pulse input to load PGM and SSEG numbers
JOG 54 BOOL I R pulse input for jog
RSTRT 55 BOOL I R pulse input for restart action
GHOLD 56 BOOL I R guaranteed soak hold, for sync
RESET 57 BOOL I R pulse input for reset
HOLD 58 BOOL I R pulse input for hold
RUN 59 BOOL I R pulse input for run
ADV 60 BOOL I R pulse input for advance
Static Configuration Parameters:
None