8/99 RS232 Communications Reference Manual 49
5.12 ASYS Function Block
Description
The Analog System Status Block (ASYS) is a function block and is part of the Alarm/Monitor category. It
provides read access to controller status values including those related to the Analog execution cycle. The
output may be connected to function block inputs. The outputs may also be connected to signal tags for
operator interface monitoring. The ASYS System Monitoring block is assigned block number 249. It looks
like this graphically on the Control Builder:
Logic 1 (Hi) if battery is low
Logic 1 (Hi) if there is a comm. failure to the operator interface
Logic 1 (Hi) if there is any operator panel unacknowledged alarm present
Logic 1 (Hi) if internal temperature is too high (>70C)
Logic 1 (Hi) if there is any operator panel alarm is present
Logic 1 (Hi) for one analog scan cycle after power up
Logic 1 (Hi) for one analog scan cycle after a new start of program (Program to Run)
Logic 1 (Hi) if a hardware fault is detected
Logic 1 (Hi) if a function block fails to operate properly
Logic 1 (Hi) when the controller run/program/test switch is in the test mode
Time controller was off (in sec.) after power loss (available for one analog scan cycle)
Analog function block scan cycle time in sec.
Analog function block scan cycle time in min.
Dynamic Parameters:
Table 5-15 ASYS Dynamic Parameters
Parameter Index Type Use R/W Description
status 0 REAL C R block status (see section 5.2 for code list)
CYC_CNT 1 REAL C R number of control block cycles
EXCTIME 3 REAL C R control block execution time in seconds
PK_EXCTIME 4 REAL C R peak control block execution time in seconds
EXECFAULT 7 BOOL C R ON = executive fault
CYCTIME 8 REAL O R control block cycle time in seconds
CYCMINS 9 REAL O R control block cycle time in minutes
NEWSTART 10 BOOL O R ON = new start
RESTART 11 BOOL O R ON = warm start
ALM_ACTIV 12 BOOL O R ON = active alarm
ALM_UNACK 13 BOOL O R ON = unacknowledged alarm
HWOK 14 BOOL O R ON = no hardware faults (See note 6)
LOWBTRY 15 BOOL O R ON = battery is low
HITEMP 16 BOOL O R ON = high RJ temperature