Function Parameter Index Reference
112 RS232 Communications Reference Manual 8/99
5.59 STFL Function Block
Description
The STFL label stands for the Setpoint Scheduler State Flags. This block is part of the Setpoint Scheduler
category. It looks like this graphically on the Control Builder.
Dynamic Values:
Table 5-79 STFL Dynamic Values
Parameter Index Type Use R/W Description
status 0 REAL C R block status
GHOLD 1 BOOL O R ON if state = 1.0, else OFF
READY 2 BOOL O R ON if state = 2.0, else OFF
HOLD 3 BOOL O R ON if state = 4.0, else OFF
RUN 4 BOOL O R ON if state = 8.0, else OFF
STOP 5 BOOL O R ON if state = 16.0, else OFF
STFL 6 REAL I R Encoded state input (See Note 1)
Static Configuration Values
None