Function Parameter Index Reference
120 RS232 Communications Reference Manual 8/99
5.67 TOT Function Block
Description
The TOT label stands for Totalizer. This block is part of the Calculations category. It looks like this
graphically on the Control Builder.
Dynamic Parameters:
Table 5-87 TOT Dynamic Parameters
Parameter Index Type Use R/W Description
status 0 REAL C R block status (see section 5.2 for code list)
TOT 1 REAL O R total (eu)
PREI 2 BOOL O R preset indicator
IN 3 REAL I R analog input value (eu)
RPRE 4 REAL I R remote preset in eu (1 to 999999)
EN 5 BOOL I R ON enables the totalizer
RST 6 BOOL I R ON resets the totalizer
Static Configuration Parameters:
Table 5-88 TOT Static Configuration Parameters
Parameter Index Type Description
lpre 1 REAL local preset (1 to 999999)
rem 2 BOOL ON selects remote preset
decr 3 BOOL ON selects decreasing from preset