Function Parameter Index Reference
110 RS232 Communications Reference Manual 8/99
5.58 SPSA Function Block
Description
The SPSA label stands for Setpoint Scheduler Auxiliary Setpoint Block. This block is part of the
Setpoint Schedulercategory. It looks like this graphically on the Control Builder.
Dynamic Parameters:
Table 5-78 SPSA Dynamic Parameters
Parameter Index Type Use R/W Description
status 0 REAL C R block status
AUX1 1 REAL O R Auxiliary output #1
AUX2 2 REAL O R Auxiliary output #2
AUX3 3 REAL O R Auxiliary output #3
AUX4 4 REAL O R Auxiliary output #4
AUX5 5 REAL O R Auxiliary output #5
AUX6 6 REAL O R Auxiliary output #6
AUX7 7 REAL O R Auxiliary output #7
AUX8 8 REAL O R Auxiliary output #8
STA 9 REAL I R Program state (for configuration - cosmetic only)
SEG 10 REAL I R Current segment number
PGM 11 REAL I R Current program number
APV1 12 REAL I R 1
st
Aux. process variable (EU)
APV2 13 REAL I R 2
nd
Aux. process variable (EU)
APV3 14 REAL I R 3
rd
Aux. process variable (EU)
APV4 15 REAL I R 4
th
Aux. process variable (EU)
APV5 16 REAL I R 5
th
Aux. process variable (EU)
APV6 17 REAL I R 6
th
Aux. process variable (EU)
APV7 18 REAL I R 7
th
Aux. process variable (EU)
APV8 19 REAL I R 8
th
Aux. process variable (EU)