Function Parameter Index Reference
8/99 RS232 Communications Reference Manual 123
All 13 BOOL O R Alarm 1
AL2 14 BOOL O R Alarm 2
BCO 15 REAL O R Back Calculation Out (%)
ATI 16 BOOL O R Auto Tune Indicator. ON = Auto Tune in progress
PVI 17 REAL I R Process Variable Input (eu) (pv_lo <= PV <= pv_hi)
RSP 18 REAL I R Remote Set Point (% or eu per sp_units)
TRV 19 REAL I R Output Track Value (%)
TRC 20 BOOL I R Output Track Command {OFF, ON}
BIAS 22 REAL I R Remote bias value for ratio PID
Static Configuration Parameters:
Table 5-91 TPSC Static Configuration Parameters
Parameter Index Type Description
GAIN 0 REAL proportional gain, 0.1 to 1000 or proportional band, 0.1% to 1000%
[Tune Set 1]
RATE 1 REAL
derivative time, 0 or 0.1 to 10 (minutes) [Tune Set 1]
RESET 2 REAL integration time, 0.02 to 50 (minutes) or repeats per minute, 0.02 to 50
(repeats) [Tune Set 1]
pv_hi 3 REAL
pv High Range value –99999 to 99999 (default 100)
pv_lo 4 REAL
pv Low Range value –99999 to 99999 (default 0)
sp_hi_lim 10 REAL
set point high limit, -99999 to 99999 (default 100)
sp_lo_lim 11 REAL
set point low limit, -99999 to 99999 (default 0)
failsafe_hi 13 BOOL ON sets motor to 100% when in failsafe. OFF sets motor to 0% (default
OFF)
al_sp[4] 14-17 REAL alarm set points al1spl, al1sp2, al2spl, al2sp2, -99999 to 99999 (default
0)
al_hyst 22 REAL
alarm hysterysis 0 to 5 (%)
ATOUTHILIM 25 REAL
auto-tuning output high limit, 0% to 100%
ATOUTLOLIM 26 REAL
auto-tuning output low limit, 0% to 100%
FUZZY 27 BOOL
ON enables fuzzy logic overshoot suppression (default OFF)
TUNESET2 28 BOOL
Use tune set 2 (default OFF)
GAIN2 29 REAL proportional gain, 0.1 to 1000 or proportional band, 0.1% to 1000%
[Tune Set 2]
RATE2 30 REAL
derivative time, 0 or 0.1 to 10 (minutes) [Tune Set 2]
RESET2 31 REAL integration time, 0.02 to 50 (minutes) or repeats per minute, 50 to 0.02
(repeats) [Tune Set 2]
use_propband 32 BOOL
Use Gain (0) or Proportional Band (1)