F8-04 63492
Deceleration time 2
0.0s to 6500.0s
Model
dependent
s At once
F8-04
on page
280
F8-05 63493
Acceleration time 3
0.0s to 6500.0s
Model
dependent
s At once
F8-05
on page
280
F8-06 63494
Deceleration time 3
0.0s to 6500.0s
Model
dependent
s At once
F8-06
on page
280
F8-07 63495
Acceleration time 4
0.0s to 6500.0s
Model
dependent
s At once
F8-07
on page
280
F8-08 63496
Deceleration time 4
0.0s to 6500.0s
Model
dependent
s At once
F8-08
on page
280
F8-09 63497
Jump frequency 1
0.00 Hz to 655.35 Hz 0.00 Hz At once
F8-09
on page
281
F8-10 63498
Jump frequency 2
0.00 Hz to 655.35 Hz 0.00 Hz At once
F8-10
on page
281
F8-11 63499
Jump frequency
amplitude
0.00 Hz to 5.00 Hz 0.00 Hz At once
F8-11
on page
281
F8-12 63500
Jump frequency
selection during
acceleration/
deceleration
0: Disabled
1: Enabled
0 - At once
F8-12
on page
281
F8-13 63501
FWD/REV Switchover
Dead-zone Time
0.0s to 3000.0s 0.0 s At once
F8-13
on page
282
F8-14 63502
Reverse run enable
0: Reverse running allowed
1: Reverse running inhibited
0 - At once
F8-14
on page
282
F8-15 63503
Running mode when
frequency reference
below lower limit
0: Run at frequency lower limit
1: Stop
2: Run at zero speed
0 - At once
F8-15
on page
282
F8-17 63505
Normally open (NO)
input of external fault
0: Always active
1: Active only in running
0 -
At stop
F8-17
on page
282
F8-18 63506
Normally closed (NC)
input of external fault
0: Always active
1: Active only in running
0 -
At stop
F8-18
on page
283