21376 0x5380 OEM hardware
incompable Keypad display: Incomp. OEM HW
Cause Remedy Error type/response
The control unit (OEM hardware) is not
compable with the power unit (OEM
har
dware).
•
Use compable hardware.
•
Contact the OEM.
Fault
•
The inverter is disabled immediately. The
motor has no torque (coasts).
•
The error can only be reset by mains
switching.
24970 0x618A Internal fan warning Keypad display: In
ternal fan
Cause Remedy Error type/response
Warning of the internal fan. Check/replace internal fan. Warning
25216 0x6280 Trigger/funcons connected incorrectly Keypad display: P400
cong err
Cause Remedy Error type/response
The assignment direcves have not been
ob
served.
•
If the "exible I/O conguraon" is acve as
control source, the "Enable inverter" or
"Run" funcon must be connected to a
digital input in order that the motor can be
stopped again any me!
•
The use of the "St
art forward (CW)" and
"Start reverse (CCW)" funcons excludes the
use of the "Run f
orward (CW)" and "Run
reverse (CCW)" funcons, and vice versa.
Check and correct the assignment of the
triggers to the funcons.
•
With k
eypad or network control, the two
"Enable inverter 0x2631:001 (P400.01)" and
"Run 0x2631:002 (P400.02)" funcons can
also be se
t to "Constant TRUE [1]" to start
the motor.
Trouble
Related topics
4St
art, stop and rotang
direcon commands ^ 43
25217 0x6281 User-dened fault 1 Keypad display: User fault 1
Cause Remedy Error type/response
Error message is not available for the inverter
i410.
Fle
xible I/O conguraon: the "Acvate fault 1"
funcon was acvated via the trigger selected
in .
Eliminate error cause and then reset error. Fault
25218 0x6282 User-dened fault 2 Keypad display: User f
ault 2
Cause Remedy Error type/response
Error message is not available for the inverter
i410.
Fle
xible I/O conguraon: the "Acvate fault 2"
funcon was acvated via the trigger selected
in .
Eliminate error cause and then reset error. Fault
Diagnoscs and fault eliminaon
Error codes, causes and remedies
296