PRE-OPERATION INSTRUCTIONS
Table 12: BACnet/IP Server Specifications
Standard Device Profile
(Annex L)
BACnet Application Specific Controller (B-ASC)
BACnet Interoperability
Building Blocks (BIBB)
ReadProperty-B (DS-RP-B), ReadPropertyMultiple-B (DS-RPM-B),
WriteProperty-B (DW-WP-B), Dynamic Device Binding-B (DM-DDB-B),
Dynamic object Binding-B (DM-DOB-B)
Segmentation Not supported
Max APDU Length 1444 bytes
Character Sets ANSI X3.4
Object Types
Analog Output, Analog Input, Analog Value, Binary Output, Binary
Input, Binary Value, Multi-state Output, Multi-state Input, Multi-state
UDP Port 47808 (0xBAC0, configurable)
Response Time Min 160us, Typical less than 1ms