INVERTER SETTINGS
36
IP Address
The IP address is created from the octet values specified in Pr. 232, Pr. 233, Pr. 234, and Pr. 235. The
value after the decimal point for each parameter value must be 0.
Subnet Mask
The subnet mask is created from the octet values specified in Pr. 236, Pr. 237, Pr. 238, and Pr. 239. The
value after the decimal point for each parameter value must be 0.
Default Gateway Address
The IP address is created from the octet values specified in Pr. 232, Pr. 233, Pr. 888, and Pr. 889. The
default gateway address can be “disabled” by setting Pr. 888 = 0 and Pr. 889 = 0. If the desired default
gateway address cannot be created using Pr. 888 and Pr. 889, the configuration studio must be used to
configure the network settings.
Example:
IP address = 192.168.16.100, Subnet mask = 255.255.255.0, Default gateway = 192.168.16.1
Set Pr. 232 = 192.00, Pr. 233 = 168.00, Pr. 234 = 16.00, Pr. 235 = 100.00, Pr. 236 = 255.00, Pr. 237 =
255.00, Pr. 238 = 255.00, Pr. 239 = 0.00, Pr. 888 = 16, and Pr. 889 = 1.