EasyManua.ls Logo

MultiTrode MultiSmart - Configuration B: Direct Communication (Recommended); Configuration C: Second Connection to DNP3 Master

MultiTrode MultiSmart
260 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
MultiSmart Installation & Operation Manual
21.1.2 Configuration B (Recommended)
In this configuration, the Pump Station receives the level over a direct communications link with the
Reservoir Monitor. This is the preferred configuration.
The Pump Station must be configured as a DNP Master (choosing remote level and configuration B for the
pump station will ensure this is the case).
Pump Station Reservoir
Slave
MTU
Master
Slave
Master
Slave
Figure 155 - Communications Configuration B
21.1.3 Configuration C
This configuration is also used when there is no direct communications link between the Pump Station and
the Reservoir Monitor. In this mode, the Pump Station will establish a second connection to the DNP3 Master
(MTU) in order to retrieve levels from the Reservoir Monitor.
This configuration can be used instead of Configuration A when there is no redundant MTU available.
When using this configuration Connection Manager must be enabled on the Pump Station. The Pump
Station must also be configured as a DNP Master (choosing remote level and configuration B for the pump
station will ensure this is the case).
Slave
Reservoir
Slave
MTU
Master
Pump Station
Master
Slave
Figure 156 - Configuration C
NOTE:
Connection manager is functionality which should be enabled as standard on the MultiSmart. Check
the software modules screen to ensure this is the case.
Page 182 of 260 MultiSmart_IO_Manual_R20

Table of Contents

Other manuals for MultiTrode MultiSmart