6. Operation
— 6-28 —
6.3.4. Jogging
Jogging can be proceeded via either the signals of control Input/Output or RS232C communication.
Table 6-11 below lists the parameters related to the jog operation. Refer to “9. Details of Command and
Parameter” for more details.
Table 6-11: Commands and parameters related to jog operation.
Starts a jogging operation.
OFF: Decelerates and stops.
_ON: Starts accelerating.
OFF: in the plus direction.
_ON: in the minus direction
Specifies a jogging operation in
the plus direction (one direction)
Specifies a jogging operation in
the minus direction (one
direction)
Specifies the jogging velocity.
Specifies the jogging
acceleration.
Specifies the jogging
deceleration.
0.0: Use JA.
0.1 to 800.0
Specifies the acceleration
profiling.
0: Set by CSA. (CSB only)
1: Constant acceleration
2: Modified sine
3: Modified trapezoid
4: Cycloid
5: Half sine
Specifies the deceleration
profiling.