7. Operational Function
7-19
7.2.6.4. In-position Limit: Parameter IN
This parameter states positioning accuracy.
The output IPOS closes when the absolute values in the error counter is less or equal to the setting value of
the parameter IN.
The unit is the resolution of the position sensor (pulse).
Table 7-24: Resolution of position sensor
Motor type
Resolution (count/revolution)
PS
2 621 440
For example, the following formula shows how to convert the repeatability of ± 100 seconds,
which is to be specified for a Motor, to the unit of pulse.
IN setting
=
Resolution
×
Repeatability
[degree]
360
=
2 621 440
×
100
=
202 [pulse]
360
3600
7.2.6.5. Parameter IS: In-position Stability Timer
This is to check the stability of positioning operation.
In case of the IPOS mode, the output IPOS signal might become unstable at settling stage of a positioning
if the parameter IN is set to low value (approximately IN100 or lower) even the servo gain is well tuned.
Setting the parameter IS is to prevent the problem.
In case of both CFIN mode and FIN mode, the setting of parameter IS prevents outputting IPOS signal
before the Motor settles in the position.