7. Operational Function
— 7-36 —
7.4.2. Customization of Monitor Data
You can output the readout of RS-232C communication monitors to the analog monitors.
You can freely set the offset value and the data range of monitors.
For example, the followings describe the way to monitor the velocity ripple of Motor rotation at the
rotational velocity range of 1 ±0.2 [s
-1
].
1) The monitor TV (Current velocity) monitors the velocity. Type MNTV if you wish to output the
current velocity on the first analog monitor.
:MNTV
MNR10.000;
MNY0.000;
:_
The screen indicates the default. The monitor center is set to 0 [s
-1
] (MNY0.000) and the output
range is set to ± 10 [s
-1
] (MNR10 000). Input the SP for the prompt “: (colon)”.
An input of TV/MN also set the monitor TV.
2) Set the velocity to 1 [s
-1
] at the monitor center.
MNR10.000;
MNY0.000;
:MNY1
:_
3) Set the output range to ± 0.2 [s
-1
] from the monitor center.
MNY0.000;
:MNY1
:MNR0.2
:_
Fig 7-35: How to customize an analog monitor
Outputs analog data monitored by
the TV (Rotation velocity)
Velocity readout ranges is ± 0.2
[s
-1
]agaisnt the monitor center.
Monitor center (2.5 [V])
corresponds to 1.0 [s
-1
] of
the velecity data.