7. Operational Function
— 7-1 —
7. Operational Function
7.1. Control Input
7.1.1. Emergency Stop: EMST
The input EMST turns the Motor servo off and stops the Motor by the dynamic brake.
Table 7-1: Signal logic of the input EMST (shipping set: normally closed)
The shipping set of polarity of the input EMST is the normally closed contact (B contact). It can
be changed to the normally open contact. Refer to “8.1.3.1. Editing Control Input Function” for
the way of changing the polarity.
If the input EMST is turned OFF, the Motor servo is off and it stops by the dynamic brake.
No operation commands are accepted while the input EMST is OFF.
The output DRDY (Driver Unit ready) opens in the state of emergency stop.
Table 7-2: State of emergency stop
Command TA (Tell alarm status)
The state of emergency stop may not be established if the input EMST signal is not being OFF longer than
1 [ms].
Fig 7-1: Signal timing of the input EMST.
Ouput IPOS
(FW < 0: CFIN)
(FW = 0: IPOS)
Output IPOS
(FW > 0: FIN)
Max. 170 ms (Max. 3.2 s
)
1
1) It takes 3.2 seconds to activate the Motor
servo for the first time after turning on the
main power.