11. Alarm and Warning
— 11-5 —
11.2. List of Alarm and warning
11.2.1. Normal State
The table below shows the condition of the System when the input SVON (Servo on) is activated and the
System is ready for the operation command, the System.
For the execution of operation, clear the input STP (Stop).
Table 11-3: The condition for command acceptance
Caution : The outputs DRDY (Driver ready), WRN (Warning) and OTPA/OTPM
(Travel limit) are normally closed and they open for reporting abnormality.
The shipping set of the outputs WRM and OTPA/OTMA is negative logic.
If the Motor does not move even no alarm or warning is reported, the System may be in the condition
shown in “Table 11-4: condition when the Motor does not move even in normal state.”
In the condition shown in the table below, the Motor gets in the servo-off state and the dynamic
brake is functioning to brake the Motor.
When the initialization of the CPU takes longer than 10 seconds at the power-on, the control
circuit is not functioning normally. Refer to “11.3.1. CPU Error” for the cause and remedy.
Table 11-4: condition when the Motor does not move even in normal state