8. More Advanced Function
8-38
Getting back to a grid position.
The current position is not necessarily on a grid specified by the parameter QR when the power is turned
on or the Motor stops in an exceptional occasion because of an alarm or a warning.
In such a case, you may position the Motor to the nearest grid by an execution of incremental user scale
positioning.
For example in the figure below, the current position is in the range of grid 1, but not on the grid 1.
Command IQ1
If the command IQ1 is executed at this moment, the Motor moves to the grid 2. That is, the
Motor moves to the first grid from the current position.
Execute the command IQ0 to move the Motor to the original grid position, which is the base
point of the current position. That is, the Motor moves to the grid 1.
Fig 8-19: Getting back to a grid in the user scale positioning
Move to the grid in the plus
direction (In case of IQ1)
Move to the grid in the minus
direction (In case of IQ0)
1
0
2
3
0° Home position
180°
90°
270°
Count up
Range 0
Current
position
1
0
2
3
0° Home position
Count up
Current
position
Range 1
Range 3
Range 2
Range 0
Range 1
Range 3
Range 2
180°
270°
90°