3. Unpacking, Installation and Wiring
— 3-14 —
Fig 3-13: Signal timing for Power on and Servo on
170 ms max. (3.2 s max.)
Control power
Main power
DRDY output
SVON input
SVSToutput
Operation command effective
It takes approximately 170 ms to turn the servo on after the input SVON (Servo ON)
is activated. (It takes 3.2 seconds for the first input of the SVON after the power is
on.). Confirm condition of the output SVST (Servo state), then start the operation.
Caution : Turn on the input SVON after the main power is on. Turn off the input
SVON before the main power is off. If the main power is off leaving the
SVON input ON, the Warning P5 (Main power under voltage) occurs.
Refer to “7.1.4. Servo on: SVON” for turning on and off of the main power.
Input of the input ACLR (Alarm clear), the command CL (Clear alarm), or turning
on the power again will clear the warning.
Caution : The cogging torque is generated because a permanent magnet is built
into this motor. Therefore, rotors might move slightly at servo off and the
power-off.
The cogging torque is magnetic suck power generated when the rotor is moved
while non-excited.