4-195
4-4 Communication Function
4
Functions
1319h Overload limit selection 2 b024 R/W
00: OFF (Disabled)
01: ON-Acc/Cnst (Enabled in
acceleration/constant speed
operation)
02: ON-Cnst (Enabled during constant
speed operation)
03: ON-A/C (R) (Enabled in acceleration/
constant speed operation
(accelerates during regeneration))
131Ah Overload limit level 2 b025 R/W
0.20 x Rated current to 2.00 x Rated
current (0.4 to 55 kW)
0.20 x Rated current to 1.80 x Rated
current (75 to 132 kW)
0.1 [A]
131Bh Overload limit parameter 2 b026 R/W 0.10 to 30.00 0.01 [s]
131Ch
Overcurrent suppression
function
b027 R/W
00: OFF (Disabled)
01: ON (Enabled)
131Dh
Active Frequency
Matching restart level
b028 R/W
0.20 x Rated current to 2.00 x Rated
current (0.4 to 55 kW)
0.20 x Rated current to 1.80 x Rated
current (75 to 132 kW)
0.1 [A]
131Eh
Active Frequency
Matching restart
parameter
b029 R/W 0.10 to 30.00 0.01 [s]
131Fh
Starting frequency at
Active Frequency
Matching restart
b030 R/W
00: Off FQ (Frequency at interruption)
01: Max.FQ (Max. frequency)
02: Set FQ (Set frequency)
1320h Soft lock selection b031 R/W
00: Lock (SFT) (Data other than b031
cannot be changed when terminal
SFT is ON)
01: Only FQ (SFT) (Data other than b031
and the specified frequency parame-
ter cannot be changed when terminal
SFT is ON)
02: Lock (Data other than b031 cannot be
changed)
03: Only FQ (Data other than b031 and
the specified frequency parameter
cannot be changed)
10: RUN chg mode (Data other than pa-
rameters changeable during opera-
tion cannot be changed)
1321h Not used 
1322h Not used 
1323h
RUN time/Power ON time
setting
b034
(HIGH)
R/W
0 to 65535 1 [h]
1324h
b034
(LOW)
R/W
1325h
Rotation direction limit
selection
b035 R/W
00: FREE (Forward and Reverse are
enabled)
01: FWD (Only Forward is enabled)
02: REV (Only Reverse is enabled)
1326h
Reduced voltage startup
selection
b036 R/W
0: (Reduced voltage startup time: Short)
to 255: (Reduced voltage startup time:
Long)
Register
No.
Function name
Function
code
R/W Monitor and setting parameters
Resolu-
tion