4-196
4-4 Communication Function
4
Functions
1327h Display selection b037 R/W
00: All (Complete display)
01: Utilized (Individual display of
functions)
02: User (User setting)
03: Compare (Data comparison display)
04: Basic (Basic display)
1328h Initial screen selection b038 R/W 000 to 202
1329h
User parameter automatic
setting function selection
b039 R/W
00: OFF (Disabled)
01: ON (Enabled)
132Ah Torque limit selection b040 R/W
00: 4-quadrant (Four-quadrant separate
setting)
01: TRQ input (Terminal switch)
02: [O] input (Analog Input)
03: Option 1
04: Option 2
132Bh
Torque limit 1
(Four-quadrant mode
forward power running)
b041 R/W
0 to 200 (0.4 to 55 kW)/
0 to 180 (75 to 132 kW)
no (Torque limit disabled)
1 [%]
132Ch
Torque limit 2
(Four-quadrant mode
reversed regeneration)
b042 R/W
0 to 200 (0.4 to 55 kW)/
0 to 180 (75 to 132 kW)
no (Torque limit disabled)
1 [%]
132Dh
Torque limit 3
(Four-quadrant mode
reversed power running)
b043 R/W
0 to 200 (0.4 to 55 kW)/
0 to 180 (75 to 132 kW)
no (Torque limit disabled)
1 [%]
132Eh
Torque limit 4
(Four-quadrant mode
forward regeneration)
b044 R/W
0 to 200 (0.4 to 55 kW)/
0 to 180 (75 to 132 kW)
no (Torque limit disabled)
1 [%]
132Fh
Torque LADSTOP
selection
b045 R/W
00: OFF (Disabled)
01: ON (Enabled)
1330h
Reverse rotation
prevention selection
b046 R/W
00: OFF (Disabled)
01: ON (Enabled)
1331h
to
1332h
Not used 
1333h Dual rate selection b049 R/W
00: CT (Constant torque)
01: VT (Variable torque)
1334h
Selection of non-stop
function at momentary
power interruption
b050 R/W
00: OFF (Disabled)
01: V-Cnst (STOP) (Enabled
(Deceleration stop))
02: NS1 (Enabled (without recovery))
03: NS2 (Enabled (with recovery))
1335h
Starting voltage of
non-stop function at
momentary power
interruption
b051 R/W 0.0 to 1000.0 0.1 [V]
1336h
Starting deceleration level
of non-stop function at
momentary power
interruption
b052 R/W 0.0 to 1000.0 0.1 [V]
1337h
Deceleration time of
non-stop function at
momentary power
interruption
b053
(HIGH)
R/W
0.01 to 3600.00 0.01 [s]
1338h
b053
(LOW)
R/W
Register
No.
Function name
Function
code
R/W Monitor and setting parameters
Resolu-
tion

Table of Contents