App-32
Appendix-1 Parameter List
Appendix
Communication function
C071
Communication
speed selection
(Baud rate selection)
[Comm. baud rate]
02: Loop-back test
03: 2400 bps
04: 4800 bps
05: 9600 bps
06: 19200 bps
05 No
4-146
C072
Communication
station No. selection
[Modbus address]
1 to 247 1 No
C073
Communication bit
length selection
[Comm. Data length]
7: 7-bit
8: 8-bit
8 No
C074
Communication
parity selection
[Parity]
00: No parity
01: Even
02: Odd
00 No
C075
Communication stop
bit selection
[Stop bit]
1: 1-bit
2: 2-bit
1No
C076
Communication error
selection
[Comm.error mode]
00: Trip
01: Decel-Trip (Trip after deceleration stop)
02: Ignore
03: Free-RUN (Free-run stop)
04: Decel-Stop (Deceleration stop)
02 No
C077
Communication error
timeout
[Comm. Timeout]
0.00 to 99.99 0.00 No s
4-104
4-146
C078
Communication wait
time
[Comm.wait time]
0 to 1000 0 No ms
4-146
C079
Communication
method selection
[Comm.mode]
00: ASCII
01: ModBus-RTU
01 No
Adjustment
C081
O adjustment
[[O] span calibration]
0 to 65535
Factory
default
Yes
C082
OI adjustment
[[OI] span calibration]
0 to 65535
Factory
default
Yes
C083
O2 adjustment
[[O2] span
calibration]
0 to 65535
Factory
default
Yes
C085
Thermistor
adjustment
[PTC span
calibration]
0.0 to 1000.0
Factory
default
Yes 4-75
C091
Debug mode
selection
[Debug mode select]
Use "00".
* Do not change.
00 No
Parameter
No.
Function name Monitor or data range
Default
setting
Changes
during
operation
Unit Page
* 2nd/3rd control is displayed when "SET(08)/SET3(17)" is allocated to one of multi-function inputs from C001
to C008.