10-29
10 CPU Unit Functions
CJ2 CPU Unit Software User’s Manual
10-3 Startup Settings and
Maintenance
10
10-3-5 Automatic Transfer at Startup
The following file names are used for automatic transfer at startup.
For example, specify the following start address and size for the DM Area.
Allocated DM Area Words for Special I/O Units and CPU Bus Units
DM Area:
File type Contents
Automatic transfer at
startup with parameter
file
Required?
Automatic trans-
fer at startup
without parame-
ter file
Required?
Program/net-
work symbol file
User program AUTOEXEC.OBJ Yes REPLACE.OBJ Yes
Parameter file PLC name
PLC Setup
Registered I/O tables
Routing tables
CPU Bus Unit Setup
Area
AUTOEXEC.STD Yes None ---
Data files Allocated DM Area words
for Special I/O Units and
CPU Bus Units (D20000 to
D32767)
AUTOEXEC.IOM --- REPLACE.IOM ---
DM Area (D0 to D19999) ATEXECDM.IOM --- REPLACDM.IOM ---
EM Area AUTOEM@@.IOM
(@@: 00 to 18 hex)
--- RPLCEM@@.IOM
(@@:00 to 18 hex)
---