EasyManua.ls Logo

Omron CJ2 CPU UNIT SOFTWARE - Page 365

Omron CJ2 CPU UNIT SOFTWARE
670 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
10-31
10 CPU Unit Functions
CJ2 CPU Unit Software User’s Manual
10-3 Startup Settings and
Maintenance
10
10-3-5 Automatic Transfer at Startup
The following six types of data files are used for automatic transfer at startup.
Be sure to set each of the above area types and the start addresses first when creating a data file for
automatic transfer at startup. For the storage size, set the size until the last address of the area type.
At startup, all the data on the data files in the Memory Card will be transferred starting at D20000, D0,
and E@_0. If there are not enough words for the entire area, the remaining words in the area will not be
changed.
Data Files for Automatic Transfer at Startup
Data files for automatic transfer at startup
Contents Range
Start
address
Size
Automatic transfer at
startup with parame-
ter file
Automatic transfer at
startup without
parameter file
AUTOEXEC.IOM REPLACE.IOM Allocated DM Area
words for Special
I/O Units and CPU
Bus Units (D20000
to D32767)
Partial 20000 12,768
words
ATEXECDM.IOM REPLACDM.IOM DM Area (D00000
to D19999)
Entire area 0 20,000
words
AUTOEM@@.IOM
(@@: 00 to 18)
AUTOEM@@.IOM
(@@: 00 to 18)
EM Entire area --- ---