10 CPU Unit Functions
10-36
CJ2 CPU Unit Software User’s Manual
z Basic I/O Unit Error Management
The following table gives the error information related to Basic I/O Units.
Auxiliary Area Flags and Words
Name Address Description
Basic I/O Unit Error Flag
(Non-fatal error)
A402.12 ON when an error has occurred in a Basic I/O Unit.
Basic I/O Unit Error, Rack Number A408.08 to
A408.15
Contains the binary rack number where the error
occurred (when A402.12 is ON) when an error has
occurred in a Basic I/O Unit.
Basic I/O Unit Error, Slot Number A408.00 to
A408.07
Contains the binary slot number where the error occurred
(when A402.12 is ON) when an error has occurred in a
Basic I/O Unit.
Basic I/O Unit Status Area (rack 0
slot 0 to rack 3 slot 9)
A050.00 to
A069.15
Indicates alarm status (load short-circuit protection) for
Basic I/O Units.
Interrupt Input Unit Position Error
Flag
A405.08 ON when the Interrupt Input Unit is not connected in one
of the four positions (slots 0 to 3) next to the CPU Unit on
the CPU Rack.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron CJ2 CPU UNIT SOFTWARE and is the answer not in the manual?

Omron CJ2 CPU UNIT SOFTWARE Specifications

General IconGeneral
BrandOmron
ModelCJ2 CPU UNIT SOFTWARE
CategorySoftware
LanguageEnglish

Related product manuals