Appendices
A-130
CJ2 CPU Unit Software User’s Manual
A327 A327.08 Pulse Output 3
Interrupt Feed-
ing In-progress
Flag
These flags are turned ON when an interrupt input is received
after output from pulse outputs 3 to 3 is started with the
IFEED(892) instruction.
OFF: Interrupt feeding not in progress.
ON: Interrupt feeding in progress.
Cleared Cleared • Cleared during
overseeing pro-
cessing after
completing inter-
rupt feeding.
• Refreshed when
interrupt input is
received after
starting pulse out-
put with
IFEED(892)
instruction.
A327.09 Pulse Output 3
Interrupt Feed-
ing Error Flag
This flag will turn ON if an overflow or underflow occurs when an
interrupt input is received, or when the specified number of pulses
is moved, after output from pulse outputs 3 is started with the
IFEED(892) instruction.
ON: No error.
OFF: Overflow/underflow or specified number of pulses has been
moved.
Cleared Cleared • Cleared when
IFEED(892)
instruction pro-
cessing is
started.
• Turned ON if an
overflow or under-
flow occurs when
an interrupt input
is received, or if
an overflow or
underflow occurs
while the speci-
fied number of
pulses is being
moved, after
operation is
started with the
IFEED(892)
instruction with
the origin defined.
A329 A329.00 PWM Output 2
Output In-
progress Flag
ON when pulses are being output from PWM output 2.
OFF: Stopped, ON: Outputting
Cleared Cleared Refreshed when
pulse output starts
or stops.
A329.08 PWM Output 3
Output In-
progress Flag
ON when pulses are being output from PWM output 3.
OFF: Stopped, ON: Outputting
Cleared Cleared Refreshed when
pulse output starts
or stops.
A330
to
A335
A330.00
to
A335.15
Special I/O Unit
Initializing Flags
These flags are ON while the corresponding Special I/O Unit is
initializing after its Special I/O Unit Restart Bit (A502.00 to
A507.15) is turned from OFF to ON or the power is turned ON.
The bits in these words correspond to unit numbers 0 to 95 as fol-
lows:
A330.00 to A330.15: Units 0 to 15
A331.00 to A331.15: Units 16 to 31
----
A335.00 to A335.15: Units 80 to 95
Use these flags in the program to prevent the Special I/O Unit's
refresh data from being used while the Unit is initializing. Also,
IORF(097) and FIORF(225) cannot be executed while a Special
I/O Unit is initializing.
OFF: Not initializing
ON: Initializing
(Reset to 0 automatically after initialization.)
These bits are turned OFF automatically when initialization is
completed.
Retained Cleared A502.00 to A507.15
A336 A336.00
to
A336.15
Units Detected at
Startup (Racks 0
to 3)
The number of Units detected on each Rack is stored in 1-digit
hexadecimal (0 to A hex).
Rack 0: A336.00 to A336.03
Rack 1: A336.04 to A336.07
Rack 2: A336.08 to A336.11
Rack 3: A336.12 to A336.15
Example: The following would be stored if Rack 0 had 1 Unit,
Rack 1 had 4 Units, Rack 2 had 8 Units and Rack 3 had 10 Units:
A336 = A 8 4 1
Retained Cleared ---
Address
Name Function
Status
after mode
change
Status at
startup
Write timing/
Related flags, set-
tings
Words Bits