Section 7 System Settings 7-1 Settings
NS-Designer Operation Manual
Controller Link
Click the Controller Link Tab.
1
2
3
4
5
No. Setting Details
1 Network Address
Set the network number of the Controller Link Network to which the PT is
connected. The number can be set between 1 and 127.
2 Node Address
Set the node number of the PT on the Controller Link Network. The number
can be set between 1 and 32.
3 Comm. Speed
Select the baud rate from 500 Kbps, 1 Mbps, or 2 Mbps.
4 Data Link Table
Setting
Click the Data Link Table Setting Button to display the Data Link Table
Setting Dialog Box. .Refer to page 7-14 for details.
5 Read Status
Set whether the Controller Link Status is read and set the address to which
status is read. The address can be set to between $B0 and $B 32336.
Setting Data Link Tables
Data Link tables show the way that data is linked. Data link tables can be set using Controller Link
Support Software or the CX-Net (Network Setting Tool). The data link tables can only be specified on
the NS-Designer.
Click the Data Link Table Setting Button to display the Data Link Table Setting Dialog Box.
1
2
7-14