Section 10 Transferring Data 10-3 Data Transfer Using SPMA
NS-Designer Operation Manual
Settings on the PT
Make the settings on the NS-Designer shown below. After completing these settings, transfer them to
the PT along with the screen data.
1. Select Settings - System Setting – Comm - All on the NS-Designer.
2. Set Ethernet to Enable.
3. Click the Ethernet Tab and make the following settings.
Set the same IP address as that of the PT. Here, 192.168.0.22 is set as an example.
4. Set the subnet mask of the PT. Here, 255.255.255.0 is set as an example.
5. Click the Add Button to display the IP Address Setting Dialog Box.
Set the same Node Address and IP Address as those set in the Ethernet Unit. Here, 6 is set for
Node Address and 192.168.0.6 is set for the IP Address as examples.
6. Click the OK Button.
7. Transfer the settings with the screen data to the PT. To do this, connect the PT with the computer
directly and perform standard data transfer. Do NOT transfer the data through the PLC.
Setting the Communications Method
1. Open the desired project on the NS-Designer and select File - Screen Data Transfer. The Screen
Data Transfer Dialog Box will appear.
2. Click the Comms.Method Button on the top right of the dialog box. The Comms.Setting Dialog
Box will appear.
3. Select Pass Through PLC.
4. Select the communications method between the computer and PLC. Set Serial (Toolbus).
5. Select the communications method between PLC and PT. Set Ethernet.
10-41