5. OPERATION
IMR02L04-E3
5-14
Setting procedure for program pattern
Setting procedure of the program pattern is described by using the parameters of the setting example and the
Partial setting type (Factory set value).
For Batch setting type, refer to Parameter switching [Batch setting type] of 4.5.3 Parameter
setting mode (P. 4-27).
PV/SV monitor
(Reset mode)
PV
00028
$
TM
SV
530:00000200
0 1
0 1
Program setting block
(Parameter setting mode)
PV
PROG
M:S
SV
30000000200
0 1
0 1
Setting pattern number
PV
PTN.NO
M:S
SV
53000000001
0 1
32
Press and hold the
key for
2 seconds or more to change to
Parameter setting mode.
Go to the setting display of the next parameter setting
Set Segment level and Segment time
PV
LEVEL
$
M:S
SV
5 30:000 00150
0 1
0 1
PV
L TIME
M:S
SV
030:00000150
0 1
0 1
Segment level
Segment time
PV
LEVEL
$
M:S
SV
5 00:000 00100
0 1
0 5
Segment level
PV
L TIME
M:S
SV
040:00000100
0 1
0 5
Segment time
Follow the same
setting procedure for
segment numbers 2 to
4 as the first segment.
Set Pattern number 1.
Set the level of
Segment 1 to 150 C.
Set the time of Segment 1 to
30 minutes 00 second.
Pattern number
Displays Segment
number 5.
Segment number
PV
LEVEL
$
M:S
SV
5 00:000 00000
0 1
0 6
Segment level
Displays End segment number. [Displays Maximum segment numbe
(32: factory set value) before ending the segment setting.]
Press the RESET key to
go to Reset mode.
RESET
End segment setting:
Press the PTN END direct key at the segment level screen of the
segment number 6 to end segment setting at segment number 5.
PTN END
(P.4-17, P.4-22)