Confidential 2. Product Description
English 8/2019. Rev 0.0 15
Table 2-8: Dry Contact Operation (Customer ID = 0)
Over-Voltage Protection
Under-Voltage Protection
Over-Temperature Protection
Over-Current Protection
Voltage Imbalance Error
Voltage Sensing Error
Under Temperature protection
Temperature Imbalance Error
Charge Stop Set Condition
1. Overvoltage alarm(4.25V/Cell)
2. SOC 100%
Charge Stop Release Condition
1. SOC < 97% or Discharge Current >│3A│
Set Condition: UPS closes B6, A6 contacts for more than 3 second.
Action : Battery MCCB Trip
Table 2-9: Dry Contact Operation (Customer ID = 1)
Over-Voltage Protection
Under-Voltage Protection
Over-Temperature Protection
Over-Current Protection
Voltage Imbalance Error
Voltage Sensing Error
Under Temperature protection
Temperature Imbalance Error
All MCCBs are off : 4A, 4B is closed
One of MCCB is on : 5B, 4B is closed
Set Condition: UPS opens B6, A6 contacts for more than 3 second.
Action : Battery MCCB Trip
Table 2-10: Dry Contact Operation (Customer ID = 2)
Discharge Prohibit Common
Undervoltage Protection
Overtemperature Protection
Discharge Overcurrent Protection
Discharge Prohibit
Normal Close
Discharge Prohibit
Normal Open
Overvoltage Alarm,
Overvoltage Protection
Overtemperature Protection
Charge Overcurrent Protection
Charge Prohibit
Normal Close
Charge Prohibit
Normal Open
All MCCBs are off : 4A, 4B is closed
One of MCCB is on : 5B, 4B is closed
Set Condition: UPS opens B6, A6 contacts for more than 1 second.
Action : Battery MCCB Trip
SMPS Assembly with 1 phase AC input has auxiliary connectors for the status of the SMPS.