2
Configured field sets
3
Settings for the whole monitoring case table
4
Settings for the individual monitoring case
5
Input conditions for a monitoring case
6
Field set in the monitoring case and in the cut-off path
7
Cut-off paths
8
Areas for defined cut-off behavior
9
Remove field set from a monitoring case
In the monitoring case editor, you can also define the monitoring cases with input
condit
ions and assign the field sets.
Further topics
"Monit
oring case", page 21
7.13.1 Settings for monitoring case tables
Name
In t
he Name field, enter a name for the monitoring case table that is as descriptive as
possible.
7.13.1.1 Configure switching sequence
Overview
Y
ou can specify the order in which the monitoring cases can be called.
You can specify one or two subsequent monitoring cases for each monitoring event.
If you do not specify a subsequent monitoring case for a monitoring case, then any
monitoring case may follow.
If input conditions are present that do not call up any of the defined subsequent
monitoring cases, the safety laser scanner switches all safety outputs to the OFF state.
You can specify the order of the monitoring cases as a process or in individual steps.
Process
Y
ou define one or more sequences. You can use a sequence to map the sequence of
work steps for your machine.
In all sequences, you can define a maximum of two subsequent monitoring cases for
each monitoring case.
If you do not specify a subsequent monitoring case for a monitoring case, then any
monitoring case may follow.
Individual steps
Y
ou define individually for each monitoring case which one or two monitoring cases may
follow.
If you do not specify a subsequent monitoring case for a monitoring case, then any
monitoring case may follow.
Complementary information
Y
ou can use the changeover order as an additional check of your control unit. For exam‐
ple, deviations of a vehicle from the route or a plant from the prescribed production
process can be detected.
7 C
ONFIGURATION
120
O P E R A T I N G I N S T R U C T I O N S | microScan3 – PROFINET 8021219/1ELL/2022-01-21 | SICK
Subject to change without notice

Table of Contents

Other manuals for SICK microScan3

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the SICK microScan3 and is the answer not in the manual?

SICK microScan3 Specifications

General IconGeneral
Scanning angle275°
Power supply24 V DC
Supply voltage24 V DC ± 20%
Enclosure ratingIP65
Resolution70 mm
Protective field range5.5 m
Number of fields128
InterfaceEthernet
Safety integrity levelSIL3
Performance levelPL e
Ambient temperature+50°C
Scanning range5.5 m