Installing
4.6 Installing Control Unit
Converter with the CU240B-2 and CU240E-2 Control Units
108 Operating Instructions, 01/2016, FW V4.7 SP6, A5E34259001B AC
Default setting 8: "MOP with Basic Safety"
DO 0: p0730, DO 1: p0731
AO 0: p0771[0], AO 1: p0771[1]
DI 0: r0722.0, …, DI 5: r0722.5
Motorized potentiometer setpoint after ramp-function generator: r1050
Speed setpoint (main setpoint): p1070[0] = 1050
Designation in the BOP-2: MoP SAFE
Default setting 9: "Standard I/O with MOP"
DO 0: p0730, DO 1: p0731
AO 0: p0771[0], AO 1: p0771[1]
DI 0: r0722.0, …, DI 3: r0722.3
Motorized potentiometer setpoint after ramp-function generator: r1050
Speed setpoint (main setpoint): p1070[0] = 1050
Designation in the BOP-2: Std MoP