Technical data
10.3 Technical data, Power Modules
Converter with the CU240B-2 and CU240E-2 Control Units
452 Operating Instructions, 01/2016, FW V4.7 SP6, A5E34259001B AC
3-phase 380 … 480 VAC ± 10%
3-phase 0 VAC … input voltage x 0.95 (max.)
0 Hz … 550 Hz, depending on the control mode
< LO base load input current
Overvoltage category ac-
The inverter insulation is designed for surge voltages according to overvoltage Category III.
Short-circuit current rating
≤ 65 kA rms
Pulse frequency (factory
setting)
• 4 kHz for devices with an LO base load power ≤ 90 kW
• 2 kHz for devices with an LO base load power > 90 kW
Can be set in 2 kHz steps in the range 2 kHz … 16 kHz.
If you increase the pulse frequency, the inverter reduces the maximum output current.
Current derating depending on the pulse frequency (Page 459)
Electromagnetic compatibil-
The devices are suitable for environments of categories C1 and C2 according to IEC/EN
DC braking, compound braking, dynamic braking with integrated braking chopper
Degree of protection ac-
IP20 Installation in a control cabinet required
Environmental conditions for transport in the transport packaging
Climatic environmental
The device is suitable for temperatures that conform with 2K4 according to EN 60721-3-2 in
Mechanical environmental
conditions (shocks and
The device is suitable for operation in mechanical environmental conditions that conform
with 2M3 according to EN 60721-3-2
Protection against chemical
The device is protected against damaging chemical substances that conform with 2C2 ac-
Biological environmental
The device is suitable for operation in biological environmental conditions that conform with
2B2 according to EN 60721-3-2
Environmental conditions for long-term storage in the product packaging
Climatic environmental
conditions
The device is suitable for temperatures that conform with 1K4 according to EN 60721-3-1 in
the range -25° … +55° C
Mechanical environmental
conditions (shocks and
The device is suitable for operation in mechanical environmental conditions that conform
with 1M2 according to EN 60721-3-1
Protection against chemical
The device is protected against damaging chemical substances that conform with 1C2 ac-
Biological environmental
The device is suitable for operation in biological environmental conditions that conform with