EasyManua.ls Logo

Siemens CU240B-2 - Invert Setpoint

Siemens CU240B-2
518 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Advanced commissioning
6.4 Setpoint calculation
Converter with the CU240B-2 and CU240E-2 Control Units
228 Operating Instructions, 01/2016, FW V4.7 SP6, A5E34259001B AC
6.4.2
Invert setpoint
The inverter provides an option to invert the setpoint sign using a bit. As an example, the
setpoint inversion is shown through a digital input.
In order to invert the setpoint through the digital input DI 1, connect the parameter p1113
with a binary signal, e.g. the digital input 1.
Table 6- 26 Examples of settings to invert the setpoint
Parameter
Remark
p1113 = 722.1
Setpoint inversion
Digital input 1 = 0: Setpoint remains unchanged.
Digital input 1 = 1: Inverter inverts the setpoint.
p1113 = 2090.11
Invert setpoint via control word 1, bit 11.

Table of Contents

Other manuals for Siemens CU240B-2

Related product manuals