Advanced commissioning
6.2 Inverter control
Converter with the CU240B-2 and CU240E-2 Control Units
208 Operating Instructions, 01/2016, FW V4.7 SP6, A5E34259001B AC
6.2.10.7
Configuring the IP interface
Configure communication with STARTER
STARTER provides a screen form to set the communication with the control system.
Open the dialog screen form "Control_Unit/Communication/Commissioning interface" and
activate the "Configure IP interfaces" tab
Set the DHCP mode to 0 (factory setting).
Enter the device name, address, gateway and the address for the subnet mask.
In the Activation field select “[2] Save and activate configuration”.
To activate the settings, you must switch off the inverter power supply and then switch on
again.
You can also enter or read out data using the expert list. You can find the corresponding
parameters in the number range r8909 … p8925