Advanced commissioning
6.7 Application-specific functions
Converter with the CU240B-2 and CU240E-2 Control Units
304 Operating Instructions, 01/2016, FW V4.7 SP6, A5E34259001B AC
Kinetic buffering (Vdc min control)
Kinetic buffering increases the drive availability. The kinetic buffering utilizes the kinetic
energy of the load to buffer line dips and failures. During a line dip, the inverter keeps the
motor in the switched-on state for as long as possible. One second is a typical, maximum
buffer time.
The following prerequisites must be fulfilled to practically use the "kinetic buffering" function:
● The driven load has a sufficiently high inertia.
● The application allows a motor to be braked during a power failure.
When the line supply dips or is interrupted, the DC link voltage in the inverter decreases. At
an adjustable threshold, kinetic buffering intervenes (V
DC min
control). The V
DC min
control
forces the load to go into slightly regenerative operation. As a consequence, the inverter
covers its power loss and the losses in the motor with the kinetic energy of the load. The
load speed decreases; however, during kinetic buffering, the DC voltage remains constant.
After the line supply returns, the inverter immediately resumes normal operation.
Image 6-52 Principle mode of operation of kinetic buffering