EasyManua.ls Logo

Siemens CU240B-2 - Resetting the Safety Functions to the Factory Setting

Siemens CU240B-2
518 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Commissioning
5.5 Restoring the factory setting
Converter with the CU240B-2 and CU240E-2 Control Units
Operating Instructions, 01/2016, FW V4.7 SP6, A5E34259001B AC
163
5.5.1
Resetting the safety functions to the factory setting
Procedure with STARTER
To reset the safety function settings to the factory setting without changing the standard
settings, proceed as follows:
1. Go online.
2. Open the screen form of the safety functions.
3. Select the button to restore the factory settings.
4. Enter the password for the safety functions.
5. Confirm that the parameters have been saved (RAM to ROM).
6. Go offline.
7. Switch off the inverter supply voltage.
8. Wait until all LEDs on the inverter go dark.
9. Switch on the inverter supply voltage again.
You have restored the safety functions in the inverter to the factory settings.
Exception: The password for the safety functions is not reset.