Advanced commissioning
6.2 Inverter control
Converter with the CU240B-2 and CU240E-2 Control Units
190 Operating Instructions, 01/2016, FW V4.7 SP6, A5E34259001B AC
Three-wire control, method 2
With one control command, you enable the two other control commands. You switch the
motor off by withdrawing the enable (OFF1).
You switch on the motor with the positive edge of the second control command (ON).
The third control command defines the motor's direction of rotation (reversing).
Image 6-10 Three-wire control, method 2
Table 6- 11 Function table
0 0 or 1 0 or 1 OFF1: The motor stops.
ON: Clockwise motor rotation.
1 0→1 1 ON: Counter-clockwise motor rotation.
p0015 = 20
Controlling the motor using the
digital inputs of the inverter:
Advanced setting
Interconnecting control commands with digital inputs of your choice (DI x).
BI: 2/3 wire control command 1 (enable/OFF1)
p3331[0 … n] = 722.x
BI: 2/3 wire control command 2
(ON)
Example: p3331[0] = 722.0 ⇒ if CDS 0 (index[0]) is selected, the inverter
receives its ON command via DI 0.
BI: 2/3 wire control command 3 (reversing)