Advanced commissioning
6.2 Inverter control
Converter with the CU240B-2 and CU240E-2 Control Units
182 Operating Instructions, 01/2016, FW V4.7 SP6, A5E34259001B AC
Not available with Control Units CU240B-2 and
-2 DP
Changing the function of an analog output:
Define the analog output type using
parameter p0776.
Interconnect parameter p0771 with a
connector output of your choice.
Interconnecting signals in the
inverter (Page 495)
Connector outputs are marked with
"CO" in the parameter list of the List
Defining the analog output type
The inverter offers a series of default settings, which you can select using parameter p0776:
AO 0 Current output (factory setting)
Voltage output
0 mA … +20 mA
0 V … +10 V
p0776[0] = 0
1
AO 1 Current output (factory setting)
Voltage output
0 mA … +20 mA
0 V … +10 V
p0776[1] = 0
1
If you change the analog output type, then the inverter automatically selects the appropriate
scaling of the analog output. The linear scaling characteristic is defined using two points
(p0777, p0778) and (p0779, p0780).
Image 6-5 Examples for scaling characteristics