Advanced commissioning
6.7 Application-specific functions
Converter with the CU240B-2 and CU240E-2 Control Units
300 Operating Instructions, 01/2016, FW V4.7 SP6, A5E34259001B AC
6.7.6
Automatic restart
The automatic restart includes two different functions:
The inverter automatically acknowledges faults.
After a fault occurs or after a power failure, the inverter automatically switches-on the
motor again.
The inverter interprets the following events as power failure:
The inverter signals fault F30003 (DC-link undervoltage), as the line supply voltage of the
inverter has briefly failed.
The inverter power supply fails for a long enough time so that the inverter has been
switched-off.
WARNING
Danger to life as a result of machine parts unexpectedly starting
When the "automatic restart" function is active (p1210 > 1), the motor automatically
starts after a power failure. Unexpected movement of machine parts can result in
serious injury and material damage.
Block off hazardous areas within the machine to prevent inadvertent access.
Setting the automatic restart function
If it is possible that the motor is still rotating for a longer period of time after a power failure or
after a fault, then you must also activate the "flying restart" function.
Flying restart switching on while the motor is running (Page 298)
Using p1210, select the automatic restart mode that best suits your application.
Image 6-50 Automatic restart modes