Advanced commissioning
6.3 Setpoints
Converter with the CU240B-2 and CU240E-2 Control Units
Operating Instructions, 01/2016, FW V4.7 SP6, A5E34259001B AC
221
Specifying the setpoint via the fieldbus
Interconnecting the fieldbus with the main setpoint
Image 6-22 Fieldbus as setpoint source
Most standard telegrams receive the speed setpoint as a second process data PZD2.
Table 6- 20 Setting the fieldbus as setpoint source
p1070 = 2050[1]
Interconnect the main setpoint with process data PZD2 from the fieldbus.
p1075 = 2050[1]
Interconnect the additional setpoint with process data PZD2 from the fieldbus.