Advanced commissioning
6.3 Setpoints
Converter with the CU240B-2 and CU240E-2 Control Units
220 Operating Instructions, 01/2016, FW V4.7 SP6, A5E34259001B AC
Analog input as setpoint source
Interconnecting an analog input
If you have selected a pre-assignment without a function of the analog input, then you must
interconnect the parameter of the main setpoint with an analog input.
Image 6-21 Example: Analog input 0 as setpoint source
Table 6- 19 Setting with analog input 0 as setpoint source
p1070 = 755[0]
Interconnect the main setpoint with analog input 0
p1075 = 755[0]
Interconnect the additional setpoint with analog input 0
You must adapt the analog input to the connected signal, e.g. ± 10 V or 4 … 20 mA.
Analog inputs (Page 178)