Technical data
10.4 Restrictions for special ambient conditions
Converter with the CU240B-2 and CU240E-2 Control Units
Operating Instructions, 01/2016, FW V4.7 SP6, A5E34259001B AC
475
Restrictions for special ambient conditions
Current de-rating depending on the ambient operating temperature
The Control Unit and operator panel can restrict the maximum permissible operating ambient
temperature of the Power Module.
Current derating depending on the installation altitude
Above 1000 m above sea level you must reduce the inverter output current as a result of the
lower cooling capability of the air.
Permissible line supplies depending on the installation altitude
● Installation altitude up to 2000 m above sea level
– Connection to every supply system permitted for the inverter.
● Installation altitudes between 2000 m and 4000 m above sea level
– Connection to a TN system with grounded neutral point.
– TN systems with grounded line conductor are not permitted.
– The TN line system with grounded neutral point can also be supplied using an
isolation transformer.
– The phase-to-phase voltage does not have to be reduced.