Advanced commissioning
6.2 Inverter control
Converter with the CU240B-2 and CU240E-2 Control Units
Operating Instructions, 01/2016, FW V4.7 SP6, A5E34259001B AC
177
Digital outputs
Changing the function of a digital output
To change the function of a digital output, you
must interconnect the digital output with a binector
output of your choice.
Interconnecting signals in the inverter
495)
Binector outputs are marked with "BO" in the p
a-
rameter list of the List Manual.
1)
Not available with Control Units CU240B-2 and CU240B-2 DP
Table 6- 2 Binector outputs (BO) of the inverter (selection)
Deactivating digital output
f_actual >= p1082 (f_max)
Drive ready for operation
Alarm: Motor current/torque limit
r0052.8 Setpoint/actual value discrepancy r0053.6 f_actual ≥ setpoint (f_setpoint)
The complete list of binector outputs is provided in the List Manual.
Changing the function of a digital output - Example
To output inverter fault messages via digital output DO
1,
you must interconnect DO1 with the fault messages: Set
p0731
= 52.3.
You can invert the signal of the digital output using parameter p0748.
For more information, please see the parameter list and the function block diagrams 2230 f
of the List Manual.