Advanced commissioning
6.2 Inverter control
Converter with the CU240B-2 and CU240E-2 Control Units
Operating Instructions, 01/2016, FW V4.7 SP6, A5E34259001B AC
177
6.2.2.3
Digital outputs
Changing the function of a digital output
To change the function of a digital output, you
must interconnect the digital output with a binector
output of your choice.
Interconnecting signals in the inverter
(Page
495)
Binector outputs are marked with "BO" in the p
a-
rameter list of the List Manual.
1)
Not available with Control Units CU240B-2 and CU240B-2 DP
Table 6- 2 Binector outputs (BO) of the inverter (selection)
0
Deactivating digital output
r0052.9
Process data control
r0052.0
Drive ready
r0052.10
f_actual >= p1082 (f_max)
r0052.1
Drive ready for operation
r0052.11
Alarm: Motor current/torque limit
r0052.2
Drive running
r0052.12
Brake active
r0052.3
Drive fault active
r0052.13
Motor overload
r0052.4
OFF2 active
r0052.14
Motor CW rotation
r0052.5
OFF3 active
r0052.15
Inverter overload
r0052.6
Closing lockout active
r0053.0
DC braking active
r0052.7
Drive alarm active
r0053.2
f_actual > p1080 (f_min)
r0052.8 Setpoint/actual value discrepancy r0053.6 f_actual ≥ setpoint (f_setpoint)
The complete list of binector outputs is provided in the List Manual.
Changing the function of a digital output - Example
To output inverter fault messages via digital output DO
1,
you must interconnect DO1 with the fault messages: Set
p0731
= 52.3.
Advanced settings
You can invert the signal of the digital output using parameter p0748.
For more information, please see the parameter list and the function block diagrams 2230 f
of the List Manual.